CVE-2024-22039
Siemens Cerberus Pro En Engineering Tool vulnerability
- Published12 Mar 2024
Description
A vulnerability has been identified in Cerberus PRO EN Engineering Tool (All versions < IP8), Cerberus PRO EN Fire Panel FC72x IP6 (All versions < IP6 SR3), Cerberus PRO EN Fire Panel FC72x IP7 (All versions < IP7 SR5), Cerberus PRO EN X200 Cloud Distribution IP7 (All versions < V3.0.6602), Cerberus PRO EN X200 Cloud Distribution IP8 (All versions < V4.0.5016), Cerberus PRO EN X300 Cloud Distribution IP7 (All versions < V3.2.6601), Cerberus PRO EN X300 Cloud Distribution IP8 (All versions < V4.2.5015), Cerberus PRO UL Compact Panel FC922/924 (All versions < MP4), Cerberus PRO UL Engineering Tool (All versions < MP4), Cerberus PRO UL X300 Cloud Distribution (All versions < V4.3.0001), Desigo Fire Safety UL Compact Panel FC2025/2050 (All versions < MP4), Desigo Fire Safety UL Engineering Tool (All versions < MP4), Desigo Fire Safety UL X300 Cloud Distribution (All versions < V4.3.0001), Sinteso FS20 EN Engineering Tool (All versions < MP8), Sinteso FS20 EN Fire Panel FC20 MP6 (All versions < MP6 SR3), Sinteso FS20 EN Fire Panel FC20 MP7 (All versions < MP7 SR5), Sinteso FS20 EN X200 Cloud Distribution MP7 (All versions < V3.0.6602), Sinteso FS20 EN X200 Cloud Distribution MP8 (All versions < V4.0.5016), Sinteso FS20 EN X300 Cloud Distribution MP7 (All versions < V3.2.6601), Sinteso FS20 EN X300 Cloud Distribution MP8 (All versions < V4.2.5015), Sinteso Mobile (All versions < V3.0.0). The network communication library in affected systems does not validate the length of certain X.509 certificate attributes which might result in a stack-based buffer overflow. This could allow an unauthenticated remote attacker to execute code on the underlying operating system with root privileges.
CVSS 3.1 breakdown
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:HAffected products
Remediation
Frequently asked
Is CVE-2024-22039 being actively exploited?
CVE-2024-22039 is not in the CISA KEV catalog. Its EPSS exploit probability is 0.81%.
How severe is CVE-2024-22039?
CVE-2024-22039 has a CVSS 3.1 base score of 10.0, rated critical. EPSS estimates a 0.81% probability of exploitation.
Which products are affected by CVE-2024-22039?
Affected products include Siemens Cerberus Pro En Engineering Tool, Siemens Cerberus Pro En Fire Panel Fc72x, Siemens Cerberus Pro En X200 Cloud Distribution, Siemens Cerberus Pro En X300 Cloud Distribution, Siemens Sinteso Fs20 En Engineering Tool, and 4 more.
How do I fix CVE-2024-22039?
Upgrade affected software to a fixed version, for example Siemens Cerberus Pro En Engineering Tool ip8, Siemens Cerberus Pro En Fire Panel Fc72x ip8, Siemens Cerberus Pro En X200 Cloud Distribution 4.0.5016 or later, then confirm no affected versions remain in your inventory.
How Secuno handles this
Secuno correlates vulnerabilities like CVE-2024-22039 against the real software inventory on every managed device, as each hourly inventory arrives. Rather than a static severity, each match is scored in context: exploit availability, EPSS, the asset's exposure, and business criticality decide where it lands in the queue. If an affected version is present anywhere across your portfolio, it surfaces automatically with a prioritised remediation path.