Skip to content

CVE-2024-44102

Siemens Telecontrol Server Basic remote code execution

10.0 CRITICALEPSS 1.00%
  1. Published12 Nov 2024

Description

A vulnerability has been identified in PP TeleControl Server Basic 1000 to 5000 V3.1 (6NH9910-0AA31-0AE1) (All versions < V3.1.2.1 with redundancy configured), PP TeleControl Server Basic 256 to 1000 V3.1 (6NH9910-0AA31-0AD1) (All versions < V3.1.2.1 with redundancy configured), PP TeleControl Server Basic 32 to 64 V3.1 (6NH9910-0AA31-0AF1) (All versions < V3.1.2.1 with redundancy configured), PP TeleControl Server Basic 64 to 256 V3.1 (6NH9910-0AA31-0AC1) (All versions < V3.1.2.1 with redundancy configured), PP TeleControl Server Basic 8 to 32 V3.1 (6NH9910-0AA31-0AB1) (All versions < V3.1.2.1 with redundancy configured), TeleControl Server Basic 1000 V3.1 (6NH9910-0AA31-0AD0) (All versions < V3.1.2.1 with redundancy configured), TeleControl Server Basic 256 V3.1 (6NH9910-0AA31-0AC0) (All versions < V3.1.2.1 with redundancy configured), TeleControl Server Basic 32 V3.1 (6NH9910-0AA31-0AF0) (All versions < V3.1.2.1 with redundancy configured), TeleControl Server Basic 5000 V3.1 (6NH9910-0AA31-0AE0) (All versions < V3.1.2.1 with redundancy configured), TeleControl Server Basic 64 V3.1 (6NH9910-0AA31-0AB0) (All versions < V3.1.2.1 with redundancy configured), TeleControl Server Basic 8 V3.1 (6NH9910-0AA31-0AA0) (All versions < V3.1.2.1 with redundancy configured), TeleControl Server Basic Serv Upgr (6NH9910-0AA31-0GA1) (All versions < V3.1.2.1 with redundancy configured), TeleControl Server Basic Upgr V3.1 (6NH9910-0AA31-0GA0) (All versions < V3.1.2.1 with redundancy configured). The affected system allows remote users to send maliciously crafted objects. Due to insecure deserialization of user-supplied content by the affected software, an unauthenticated attacker could exploit this vulnerability by sending a maliciously crafted serialized object. This could allow the attacker to execute arbitrary code on the device with SYSTEM privileges.

CVSS 3.1 breakdown

Attack vectorNetwork
Attack complexityLow
Privileges requiredNone
User interactionNone
ScopeChanged
ConfidentialityHigh
IntegrityHigh
AvailabilityHigh
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H

Affected products

Siemens Telecontrol Server Basic≥ 3.1 < 3.1.2.1

Remediation

Fixed in
Siemens Telecontrol Server Basic≥ 3.1.2.1

Frequently asked

Is CVE-2024-44102 being actively exploited?

CVE-2024-44102 is not in the CISA KEV catalog. Its EPSS exploit probability is 1.00%.

How severe is CVE-2024-44102?

CVE-2024-44102 has a CVSS 3.1 base score of 10.0, rated critical. EPSS estimates a 1.00% probability of exploitation.

Which products are affected by CVE-2024-44102?

Affected products include Siemens Telecontrol Server Basic.

How do I fix CVE-2024-44102?

Upgrade affected software to a fixed version, for example Siemens Telecontrol Server Basic 3.1.2.1 or later, then confirm no affected versions remain in your inventory.

How Secuno handles this

Secuno correlates vulnerabilities like CVE-2024-44102 against the real software inventory on every managed device, every day. Rather than a static severity, each match is scored in context: exploit availability, EPSS, the asset's exposure, and business criticality decide where it lands in the queue. If an affected version is present anywhere across your portfolio, it surfaces automatically with a prioritised remediation path.

Get Patch this first every Monday

Five vulnerabilities that matter this week, ranked on real exploitation. Plain language, one email, no spam.

You can unsubscribe with one click from every issue. We handle your details as described in our privacy policy.

Data from the NVD, CISA KEV catalog and FIRST EPSS. CVSS 3.1 base score shown where available.